Setup, Calibration – Rockwell Automation 931S-C3C3J-DC Active Converter User Manual

Page 7

Advertising
background image

• Setup

General
Inputs to the unit are analog current or voltage type. They are
rated for measuring category III signals with a voltage of 300 V

eff

to

earth.
The input and output type are jumper selectable and their ranges
are set by the values used during calibration.

• Calibration

General
All instruments are calibrated before leaving the factory and should
not need adjustment unless a change of range is required or until
the next scheduled calibration.

Equipment requirements
• An AB Bulletin 1606 DC Power Supply
• A digital multimeter (accurate to 0.05 mV and ±1 μA)

Procedure
1. Remove the instrument from the case and confirm that the

jumpers are in the correct positions for the input and output type
required.

Advertising