Publication 1413-UM001C-EN-P - May 2006
Add Special Functionality 53
Part 1 Example
Part 2
If KVAR_LAG_WAIT_2_ADD (B56:0/8) is high and
TOTALSTEP_AVAL_AUTO (N70:31) is greater than 0, then output
energize KVAR_LAG_ADD_STEP (B56:0/4) and unlatch
KVAR_LAG_WAIT_2_ADD (B56:0/8). This will actuate the required
step defined by the step routine.
See Part 2 Example.