Install the 1609 UPS in the Appropriate Environment

Hardwire the UPS

Wiring of the UPS should be performed by a qualified electrician using appropriate wire gauges.

Start UP

Connect Power and Equipment to the UPS

1. The UPS features a transient voltage surge-suppression (TVSS) screw

located on the front panel. The TVSS screw is used

for connecting the ground lead on surge suppression devices.

Prior to connecting the grounding cable, ensure that the UPS is NOT connected to input (utility), or battery power.

2. Wire the UPS.
3. Add optional accessories to the Network Management Card (NMC) slot.
4. Turn on all connected equipment. To use the UPS as a master on/off switch, be sure all connected equipment is switched on.

Standard Connectors

Contact Closure Port

The relays are connected from the common (COM) to the normally closed (NC) pins.When the unit enters a low battery or on battery

state, the appropriate relay will change state and connect the common (COM) to the normally open (NO) pin.

Start the UPS

Press the

button on the front panel to start the UPS.

The battery charges to 90% capacity during the first four hours of normal operation. Do not expect full battery run capability during this

initial charge period.

Do not operate the UPS where there is excessive dust or the temperature or

humidity are outside the specified limits

Mount the UPS

This unit is designed to mount on a heavy duty DIN rail or on the back panel of an

enclosure.
If mounted in an enclosure use six screws appropriate for the weight of the unit and

the mounting surface material.

1 EPO

2 EPO COM

3 NC

4 COM

5 NO

6 NC

7 COM

8 NO

LOW

BATTERY

ON

BATTERY

Contact Closure Port

(located on front panel)

Output Contact Ratings:

Parameter

Value

nominal switching capacity

1 A @ 30 VDC

maximum switching power

30 W

maximum switching voltage

60 VDC

maximum switching current

2 ADC

maximum carrying current

2 ADC

surge ratings

2 kV per Bellcore TA-NWT-001089
1.5 kV per FCC part 68

The emergency power off (EPO) feature is

user configurable. EPO provides immediate,

remote de-energizing of connected

equipment without the device switching to

battery operation.
The EPO interface is a Safety Extra Low

Voltage (SELV) circuit. Use a normally open

SELV circuit to activate the EPO.

SERIAL PORT

A special serial interface cable is included with the UPS. Because the pinout is unique, an off the

shelf cable will not be compatible with the UPS. This port enables remote configuration and

monitoring with the use of PowerChute

®

Software.

Use the cable supplied by APC.