Wiring – Rockwell Automation 1397 400-600HP AC Line Filter Kit Inst. User Manual
Page 4
 
1397 AC Line Filter Kit
4
1397-5.31 September, 1998
❐
2
Refer to Figure 2 and connect one end of each wire to one of the 
male spade terminals on each of the drive’s three AC input bus 
bars. Connect the other end of these wires to the three male spade 
terminals on the fuse block.
❐
1
Cut three (3) pieces of 600V, 14 AWG wire (maximum length 
1.2m (4 ft) each). These wires should be of sufficient length to 
connect the spade terminals on the fuse block to the connectors 
on each of the drive’s AC input bus bars. Terminate the ends of 
each wire with the female spade terminals provided in the kit.
Wiring
Wire the AC Line Filter Kit as follows:
❐
3
Connect the spade terminals on one end of the wire harness 
supplied in the kit to each of the three male terminals on the 
capacitor assembly. Connect the spade terminals on the other 
end of the wire harness to the three remaining male spade 
terminals on the fuse block.
❐
4
Install the three (3) 7.5A fuses provided in the kit into the fuse 
block.
❐
5
Refer to Figure 2 and install the plastic cover using four (4) M4 
flat washers and four (4) M4 x 12 self-threading screws. Tighten 
to 1.4 Nm (12 in-lb).