Mounting Requirements
Dynamic brake enclosures must only be installed in the vertical
position. Select a location using the following guidelines.
• Each dynamic brake enclosure must be mounted outside of any other
enclosure or cabinet and exposed to unrestricted circulating air for
proper heat dissipation. Allow a minimum of 304.8 mm (12 in.)
between brake enclosures and all other enclosures or cabinets
including the drive.
• The brake enclosure must be mounted within 30 m (100 ft.) of the
drive.