Terminal block wiring capacity, Setup, Wiring scheme – Rockwell Automation 1305 DYNAMIC BRAKES User Manual
Page 11

1305 Dynamic Brake
11
1305-5.11 May, 1999
BULLETIN 1305
DB Enable
Parameter 11
GND GND L1
R1
L2
S
L3
T
+DC BRK
(-DC)
TI
U
T2
V
T3
W
1305 BRAKE
BRK GND +DC
Terminal Block Wiring
Capacity
Screw Size, Wire Size and Torque Specifications.
Terminal
Screw Size
Maximum/Minimum Wire Size
Maximum Torque
TB1
M4
4/0.75 mm (10/18 AWG)
1.81 N-m (16 lb-ins.)
Setup
ATTENTION: The dynamic brake unit contains a
thermostat to guard against overheating and component
damage.
If the duty cycle, torque setting and/or ambient temperature
exceeds the specifications listed in this publication, the
thermostat is designed to trip and disable the brake.
If reduced braking torque represents a potential hazard to
personnel, auxiliary stopping methods must be considered in
the machine and/or control circuit design.
!
P.011
— Set
DB Enable
to
Enable
This parameter must be set to enable when dynamic braking is
installed. Refer to your 1305 User Manual for programming
procedures and record the changes for future reference.
Wiring Scheme