B-c jumper settings, P.272 [e-fld volts adj – Rockwell Automation 1397 Enhanced Field Supply Csrd User Manual

Page 11

Advertising
background image

1397–5.12 June, 1997

1397 Enhanced Field Supply Card

11

0

1

2

3

4

5

6

7

8

9

000

0.4502

0.4502

0.4503

0.4505

0.4507

0.4510

0.4514

0.4518

0.4523

0.4529

010

0.4536

0.4543

0.4551

0.4559

0.4568

0.4578

0.4589

0.4600

0.4612

0.4624

020

0.4637

0.4651

0.4665

0.4681

0.4696

0.4712

0.4729

0.4747

0.4765

0.4784

030

0.4803

0.4823

0.4844

0.4865

0.4886

0.4909

0.4931

0.4955

0.4979

0.5003

040

0.5028

0.5054

0.5080

0.5106

0.5133

0.5161

0.5189

0.5217

0.5246

0.5276

050

0.5306

0.5336

0.5367

0.5398

0.5429

0.5461

0.5494

0.5527

0.5560

0.5593

060

0.5627

0.5661

0.5696

0.5731

0.5766

0.5801

0.5837

0.45873

0.5909

0.5946

070

0.5983

0.6020

0.6057

0.6094

0.6132

0.6170

0.6208

0.6246

0.6284

0.6323

080

0.6362

0.6400

0.6439

0.6478

0.6517

0.6556

0.6595

0.6635

0.6674

0.6713

090

0.6752

0.6792

0.6831

0.6870

0.6909

0.6940

0.6988

0.7027

0.7066

0.7104

100

0.7143

0.7182

0.7220

0.7259

0.7297

0.7335

0.7373

0.7410

0.7448

0.7485

110

0.7522

0.7559

0.7596

0.7632

0.7668

0.7704

0.7739

0.7774

0.7809

0.7844

120

0.7878

0.7912

0.7945

0.7978

0.8011

0.8043

0.8075

0.8107

0.8138

0.8169

130

0.8199

0.8229

0.8258

0.8287

0.8316

0.8344

0.8371

0.8398

0.8425

0.8451

140

0.8477

0.8502

0.8526

0.8550

0.8573

0.8596

0.8618

0.8640

0.8661

0.8682

150

0.8702

0.8721

0.8740

0.8758

0.8775

0.8792

0.8809

0.8824

0.8838

0.8854

160

0.8867

0.8881

0.8893

0.8905

0.8916

0.8926

0.8936

0.8945

0.8954

0.8962

170

0.8969

0.8975

0.8981

0.8986

0.8991

0.8995

0.8998

0.9000

0.9002

0.9003

180

0.9003

B-C Jumper Settings

Enhanced Field Supply Jumper Set to B-C

Drive

Minimum Output

Maximum Output

Input Volts

Motor Field Volts

Motor Field Volts

230V AC

0.45V DC

0.9V DC

LINE

CT

707973-5R

SP4

582

583

581

F1/37

F2/35

FC3

B

C

A

FC2

FC4

P4

P4

P4

X1

X2

H2

H1

Example

A 230V AC, 60Hz input is connected to the drive. The drive’s output is
connected to a 15HP DC motor with a nameplate field voltage of
150V DC.

The Line Multiplier =

150 = 0.6522
230

0.6522 is within the B-C jumper range of 0.45-0.9. In the B-C Jumper
Settings table, 0.6522 is closest to 0.6517. Therefore:

1. Set Enhanced Field Supply Jumper to B-C.

2. Set drive Regulator Board Jumper J21 to B-C.

3. Set parameter

P.272 [E-Fld Volts Adj]

to 84 —

080 + 4

.

P.272

Advertising