1397–5.12 June, 1997

1397 Enhanced Field Supply Card

9

Setup

(3) drive parameters, Jumper 21 on the drive’s Regulator Board, and
the Enhanced Field Supply Card’s jumper wire must be set to
configure the Enhanced Field Supply Card.

P.050 — Nominal AC Freq

This parameter must be set to match the AC input line’s frequency.

P.273 — Fld Econ Delay

Some motor fields may not be able to withstand the power dissipated
under full field voltage with the motor stoped. Parameter

P.273 [Fld Econ Delay]

allows a fixed reduction of field voltage to be set

for a user specified amount of time while the motor is stopped. When
restarted, the motor will be returned to the full field output voltage
level set by

P.272 [E-Fld Volts Adj]

.

Installation

(continued)

❏ 10 If required, reinstall the auxiliary panel cover or AC line

disconnect removed in steps 4a

&

4b. Torque the (3) bus bar

fasteners to the values listed below.

Fastener Size

Maximum Torque

1

4

7.46 N-m (66 lb.-in.)

3

8

26.66 N-m (236 lb.-in.)