Step 5 - Wire AC Power to the Unit and Ground the Unit
1329I-5.5 Integrated Drive/Motor — January, 2000
• Connect the incoming three phase AC line to terminals R, S, and T, as shown in
• Connect the incoming single phase AC line to any two of the terminals R, S, and T,
as shown in Figure 5.2.
Figure 5.2
Grounding the Unit
5.1
Grounding the Unit
Connect the ground wire brought in with the incoming AC power to the unit’s grounding
screw ➊ (see Figure 5.2). This grounding conductor must run unbroken from the unit
to earth ground.
➊
Recommended tightening torque is 2.6 N-m (32 lb.-in.).
PE
PE
DC+
DC-
DBR
T/L3
S/L2
R/L1
DC+
DC-
DBR
T/L3
S/L2
R/L1
DC Bus
(Do not wire.)
Not Used
AC Inputs
Ground/Protective Earth
AC Input Terminal
ATTENTION: The user is responsible for conforming with all local,
national, and international codes applicable to the grounding of this
equipment. Failure to observe this precaution could result in severe bodily
injury or loss of life.