Connect 1609-EXBAT to the UPS

The 1609-D can be used with the External Battery Unit (1609-EXBAT). The 1609-EXBAT is designed to mount

to a heavy duty din-rail (see Diagram 3) or the optional mounting bracket assembly (1609-BRK) which will

allow it to mount to either the panel or floor (see Diagram 4).

To install the 1609-EXBAT with the 1609-D UPS, connect the three 10 AWG wires from the 1609-EXBAT

terminals to the 1609-D terminals marked as ‘EXTERNAL BATT PACK (36V)’ (see Diagram 2).
Dispose of used batteries according to the battery instructions.

Diagram 3 - Heavy Duty DIN Rail Mount Diagram 4 - Panel or Floor Mount

The following precautions should be observed when working on batteries:

1) Remove watches, rings, or other metal objects.

2) Use tools with insulated handles.

3) Do not lay tools or metal parts on top of batteries.

4) Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from

ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of

such shock can be reduced if such grounds are removed during installation and maintenance.

Service Instructions

a) Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and

the required precautions. Keep unauthorized personnel away from the batteries.

b) When replacing batteries, replace with the same number of the 1609 battery packs supplied by Rockwell

Automation.

Recommended Battery for use with the UPS and External Battery Cabinet

Rockwell Automation battery catalog numbers 1609-SBAT and 1609-HBAT consists of the battery

manufacturers listed below:

Not for use in a computer room as defined in the Standard for the Protection of Electronic Computer/Data

Processing Equipment, ANSI/NFPA 75.
Refer to NEC Table C.1 for North America market application. If using 3 x 10 AWG wires (excluding the wire

type RHH), the suggested trade size for EMT is 1/2 inch and knockout hole diameter dimension of 22.2 mm.
Dispose of used batteries according to the battery instructions.

Manufacturer

Rating

Type

B & B Battery (USA) INC. (MH19884)

GS Yuasa International Ltd. (MH12970)

Shenzhen Center Power Tech. Co., Ltd. (MH25860)

12 Vdc, 2.75 Ah

12 Vdc, 5.0 Ah

12 Vdc, 2.75 Ah

12 Vdc, 3.375 Ah

HRL5.5 - 12

BP 5-12

HR5.5 - 12

SHR7 - 12

NPH5 - 12

CP1250

Shenzhen Ritar Power Co., Ltd. (MH28539)

RT1250

CSB Battery Co., Ltd. (MH14533)

HR1221W

12 Vdc, 5.0 Ah

12 Vdc, 5.0 Ah

12 Vdc, 5.0 Ah

12 Vdc, 5.25 Ah

Warning: Do not dispose of battery or batteries in a fire. The battery may explode. Do not open or mutilate the battery or
batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. A battery can present a risk of electrical
shock and high short circuit current.

Bulletin 1609 Industrial Uninterruptible Power Supply

6

Publication 1609-IN012B-EN-P - August 2012 DIR 10000234085 (Version 01)

Advertising