7
Coordination of Insulation according to EN 50178, 04.98
(Safe Distance)
Rated Voltage
300 V
Rated surge Voltage
6 kV
Overvoltage category
III
Contamination class
2
Clearance and
creepage distances
≥ 5.5 mm
Isolation voltage
Voltage endurance
Input/output
4 kV
eff
/1 s
Input/output/to mounting rail
4 kV
eff
/1 min
Connection data
Connection
BLZ/SL
Insulating stripping length
8 ± 0.5 mm
Solid core
0.5 ... 2.5 mm
2
Flexible core
0.5 ... 2.5 mm
2
With ferrules
0.5 ... 1.5 mm
2
Advertising