3 FLEX I/O DC Power Supply Modules

Publication 1794-IN069D-EN-P - June 2004

Example of Using a 1794-PS13 Power Supply to
Power 4 Adapter Modules

Diagnostic Indicator

The power supplies have 1 indicator.

Specifications

24V dc

ac

24V dc

120V ac

All dc powered I/O modules

All ac powered I/O modules

24V dc

24V dc from separate source

24V dc from separate source

Combination ac and dc powered I/O modules

Power
Supply

Adapter

Adapter

Adapter

ac

24V dc

All ac powered I/O modules

Adapter

Power

Indicator

The power indicator is on (green) when voltage
at the output is between 20.4V dc and 28V dc.

Power

24V DC

POWER SUPPLY

1794-PS13

24V

COM

Power

Indicator

Power

24V DC

POWER SUPPLY

1734-PS3

24V

COM

The power indicator is on (green) when voltage
at the output is between 20.4V dc and 28V dc.

1794-PS13

1794-PS3

Indicator

Description

ON (green)

Output voltage is greater than 20.4V dc, but less than 28V dc

OFF

No power applied to power supply

Output voltage exceeded 35V dc, and overvoltage protection
shut the unit down

Output current is above 1.4A (1794-PS13) or above 3.2A
(1794-PS3)

Specifications - Cat. No. 1794-PS13 and 1794-PS3

1794-PS13

1794-PS3

Nominal Supply Voltage

120V ac, 47-63Hz; 0.6A max.
230V ac, 47-63Hz; 0.42A max.

120V ac, 47-63Hz; 1.7A max.
230V ac, 47-63Hz; 1.1A max.

Voltage Range

85-265V ac

Input Current

0.7 maximum

1.9A maximum

Inrush Current

40A typical, 1 ac cycle @ V

in

265V ac, 55°C

Interruption

Output will stay within specification when input drops out for 1/2 cycle @
47Hz, 85V ac with maximum load

Output Specifications

Nominal Output

+24V dc

Voltage Range

20.4-27.6V dc (includes noise and 5% ac ripple)

Output Current

1.3A maximum

3A maximum (horizontal mount),
2.8A all other mounting (See
derating curve)

Output Power

31.2W

72W

Output Ripple

1200mV peak-to-peak maximum

Minimum Load

0mA

50mA

Output Surge

Sufficient to drive 4 adapters

Sufficient to drive 10 adapters

Overvoltage Protection

Output internally limited to 35V dc. Cycle power to reenergize.

Leakage Current

0.5mA rms maximum @ rated input and output

Isolation Voltage

Tested at 2500V dc for 1s

Overcurrent Protection

1.4A minimum

3.2A minimum

Thermal Dissipation

23.9 BTU/hr

41.0 BTU/hr

Power Dissipation

7W maximum

12W maximum

Dimensions

3.4H x 2.7W x 2.7D inches
87H x 69W x 69D mm

3.4H x 3.7W x 2.7D inches
87H x 94W x 69D mm

General Specifications

Environmental Conditions

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 55°C (32 to 131°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):
–40 to 85°C (–40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating

Damp Heat):
5 to 95% non-condensing

Vibration

IEC60068-2-6 (Test Fc, Operating):
5g @ 10-500Hz

Shock

IEC60068-2-27 (Test Ea, Unpackaged shock)
Operating 30g
Non-operating 50g

Emissions

CISPR 11:
Group 1, Class A (with appropriate enclosure)

ESD Immunity

IEC 61000-4-2:
4kV contact discharges
8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 1000MHz

EFT/B Immunity

IEC 61000-4-4:
±2kV at 5kHz on power ports

Surge Transient Immunity

IEC 61000-4-5:
±1kV line-line(DM) and ±2kV line-earth(CM) on ac power ports

Conducted RF Immunity

IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz

Enclosure Type Rating

None (open-style)