Copyright © 2004 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

Derating Curve for 1794-PS3 (for any mounting other than
horizontal)

Mounting Dimensions

Conductors

Wire Size

Category

1

22 to 12 AWG (0.34mm

2

- 2.5mm

2

) stranded copper wire rated at 75°C or

higher
3/64 inch (1.2mm) insulation maximum
2

Terminal Screw Torque

7 pound-inches (0.8Nm)

Certifications (when product is
marked)

2

C

UL

US

UL Listed Industrial Control Equipment for Class I, Division

2, Groups A, B, C and D Hazardous locations

C

UL

US

UL Listed Industrial Control Equipment, certified for US

and Canada

CE

2

European Union 89/336/EEC EMC Directive,

compliant with:

EN 61000-6-4; Industrial Emissions

EN 50082-2; Industrial Immunity

EN 61326; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

European Union 73/23/EEC LVD Directive, compliant

with:

EN 61131-2; Programmable Controllers

C-Tick

2

- Australian Radiocommunications Act compliant with:

AS/NZS CISPR 11, Industrial Emissions

1

You use this category information for planning conductor routing as described in Allen-Bradley
publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines.

2

For the latest up-to-date information, see the Product Certification link at www.ab.com for Declarations of
Conformity, Certificates and other certification details. For notification of any additional release notes, refer to

www.ab.com/manuals/

0

0.5

0

2.0

1.0

3.0

10

20

30

40

50

55

60

Max.

Output

Current

(A)

Ambient Temperature

oC

The area within the curve represents the safe operating range for the module under
various conditions of user supplied 24V dc supply voltages and ambient temperatures.

= Normal mounting safe operating range, (includes ).

= Other mounting positions (including inverted horizontal) safe operating range

2.8

2.5

1.5

Normal Mounting – Horizontal

Other Mounting (including Vertical, and Inverted Horizontal Mounting)

Inches

(Millimeters)

3.4

(87)

3.2

(80)

2.7

(68)

.83 (21)

1794-PS13

3.4H x 2.7W x 2.7D
(87H x 68W x 69D)

1.4

(35)

A

2.3

(59)

A

= Mounting hole dimensions for optional mounting kit

B

B

= DIN rail

2.0

(50)

1.2

(28)

C

C

= Secure DIN rail approximately every 200mm

Power

24V DC

POWER SUPPL Y

1794-PS13

24V

COM

Inches

(Millimeters)

3.4

(87)

3.2

(80)

3.7

(94)

1794-PS3

3.4H x 3.7W x 2.7D
(87H x 95W x 69D)

A

B

= DIN rail

2.0

(50)

1.2

(28)

B = Secure DIN rail approximately every 200mm

Power

24V DC

POWER SUPPLY

1794-PS3

24V

COM

A

1794-PS13

1794-PS3

Advertising