Back cover – Rockwell Automation 1787-DNPS DeviceNet Power Supply Installation Instructions User Manual

Page 4

Advertising
background image

Publication 1787-5.8 - February 1999

PN 955138-62

Supersedes Publication xxxxxxx-xx - xxxxxxx-xx

Copyright 1998 of Rockwell International Corporation. Printed in the U.S.A.

Table 1: Specifications

DeviceNet is a trademark of Open Device Vendor Association (ODVA).

Power
Connector

3-pin IEC

Line Frequency

48-62 Hz

Fuse

Class 2 type accepted

1

Turn-on Time
(with full load)

250msec max 95% of final
value

Size

5” x 6.5” x 11”

Isolation

output isolated from AC and
chassis ground

DC Connector

Phoenix Combicon style 5-pin 5.08mm pitch
female and mating connector

Operating Temperature

0 - 60

°

C min 0 - 75

°

C with

30% derating at 75

°

C

32 - 140

°

F min 32 - 167

°

F

with 30% derating at 167

°

F

DC Connector
Pins

Pin 1, 24V+; Pin 3, Chassis ground; Pin 5,
24V-

Storage
Temperature

-40 - 85

°

C

-40- 185

°

F

Indicators

LED power good indicator

Humidity

95% non-condensing

Mounting

Flange

Electrostatic Discharge

4KV contact 8KV air

Enclosure

Vented enclosure (indoor use)

Vibration

2g, 10-500hz

Input Voltage

115V±10%
230V±10% selectable

Shock

30g, 11ms half cycle

Output Voltage

24V dc ± 1%

Surge

4KV common mode,
2KV differential mode

Output Current

Nameplate rating of 100VA to be consistent
with NEC Class 2
Peak output currents 5.25 A

Electrical Fast Transient

2KV

Ripple

250mV

Radiated Immunity

10V/M 80 MHZ- 1GHZ

Load
Capacitance
Capability

7000uF load

Agency Certification (when
product or packaging is
marked)

1

Contact the manufacturer for information on replacing fuses for your power supply.

marked for all applicable directives

1310 class 2 power limited circuits

223 - M91 with T.I.L. No. CA 2A.

Advertising