Output specifications – Rockwell Automation 1769-OA8 Compact 100 to 240V ac Solid State Output Module User Manual

Page 15

Advertising
background image

Compact™ 100 to 240V ac Solid State Output Module 15

Publication 1769-IN055A-EN-P - April 2001

Output Specifications

Specification

1769-OA8

Voltage Category

100 to 240V ac

Operating Voltage Range

85V ac to 265V ac at 47 to 63 Hz

Number of Outputs

8

Bus Current Draw (max.)

145 mA at 5V dc (0.725W)

Heat Dissipation

2.12 Total Watts
(The Watts per point, plus the minimum Watts, with all
points energized.)

Signal Delay (max.) – resistive load

(1)

(1)

Turn On Type - Triac outputs turn ON and OFF at ac line zero cross.

turn-on = 1/2 cycle
turn-off = 1/2 cycle

Off-State Leakage (max.)

(2)

(2)

Recommended Loading Resistor - To limit the effects of leakage current through solid state outputs, a loading resistor
can be connected in parallel with your load. For 120V ac operation, use a 15K

, 2W resistor. For 240V ac operation use a

15K

, 5W resistor.

2.0 mA at 132V ac
2.5 mA at 265V ac

On-State Current (min.)

10.0 mA

On-State Voltage Drop (max.)

1.5V ac at 0.5 A

Continuous Current per Point (max.)
See the derating graphs on page 16.

0.25A at 60°C (140°F)
0.5A at 30°C (86°F)

Continuous Current Per Module (max.)
See the derating graphs on page 16.

2.0 A at 60°C (140°F)
4.0 A at 30°C (86°F)

Surge Current (max.)

(3)

(3)

Surge Suppression - Connecting surge suppressors across your external load will extend the life of the triac outputs. For
additional details, refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication 1770-4.1.

10.0A (Repeatability is once every 2 seconds for a duration
of 25 msec.)

Power Supply Distance Rating

8 (The module may not be more than 8 modules away from
the power supply.)

Output Point to Bus Isolation

Verified by one of the following dielectric tests: 1836V ac
for 1 sec. or 2596V dc for 1 sec.
265V ac working voltage (IEC Class 2 reinforced insulation)

Isolated Groups

Group 1: outputs 0 to 3
Group 2: outputs 4 to 7

Output Group to Output Group Isolation

Verified by one of the following dielectric tests: 1836V ac
for 1 sec. or 2596V dc for 1 sec.
265V ac working voltage (basic insulation)
150V ac working voltage (IEC Class 2 reinforced insulation)

Vendor I.D. Code

1

Product Type Code

7

Product Code

84