Field wiring connections, Grounding the module, Output wiring – Rockwell Automation 1769-OA8 Compact 100 to 240V ac Solid State Output Module User Manual

Page 8

Advertising
background image

8 Compact™ 100 to 240V ac Solid State Output Module

Publication 1769-IN055A-EN-P - April 2001

Field Wiring Connections

Grounding the Module

This product is intended to be mounted to a well-grounded mounting surface such
as a metal panel. Additional grounding connections from the module’s mounting
tabs or DIN rail (if used), are not required unless the mounting surface cannot be
grounded. Refer to Industrial Automation Wiring and Grounding Guidelines,
Allen-Bradley publication 1770-4.1, for additional information.

Output Wiring

Basic wiring

(1)

of output devices to the 1769-OA8 is shown below.

ATTENTION

!

Be careful when stripping wires. Wire fragments that fall into a
module could cause damage at power up. Once wiring is
complete, ensure the module is free of all metal fragments.

(1)

Surge Suppression - Connecting surge suppressors across your external load will extend the life of the triac outputs. For
additional details, refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication 1770-4.1.

100 to 240V ac

L2

L1

L2

L1

OUT6

OUT4

VAC 2

OUT2

OUT0

OUT7

OUT5

OUT3

OUT1

VAC 1

CR

CR

CR

CR

CR

CR

CR

CR

100 to 240V ac