Enable quickconnect – Rockwell Automation 1732E-XXXX ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect User Manual

Page 12

Advertising
background image

12 1732E ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect

Publication 1732E-IN010C-EN-E - June 2013

Enable QuickConnect

To enable QuickConnect for the Ethernet ports, use the RSLogix 5000 software Module
QuickConnect tab and check the Enable QuickConnect option. For more information on
the QuickConnect system set up, refer to Ethernet QuickConnect Application Technique,
publication

ENET-AT001

.

After the QuickConnect feature is set to "on", the module must be power cycled.
QuickConnect is active during the next connection.

Once active, the QuickConnect feature automatically sets all Ethernet ports to:

Speed = 100 Mbps

Duplex = Full

Auto-negotiate = Off

Automatic Cross-over Cable Detection (Auto-MDIX) = Off

If you configure BootP or DHCP, QuickConnect changes the configuration to retain the
current IP address. Disabling the QuickConnect feature automatically sets all Ethernet
ports to Automatic Cross-over Cable Detection (Auto-MDIX) = On.

To reset the Ethernet ports to Auto-negotiate or the IP address to DHCP request, you can:

change the setting on the module web page

change the setting in the RSLogix 5000 software

perform a factory reset