Certifications, Environmental specifications – Rockwell Automation 1732E-XXXX ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect User Manual

Page 22

Advertising
background image

22 1732E ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect

Publication 1732E-IN010C-EN-E - June 2013

Radiated RF immunity IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz

10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz

10V/m with 200 Hz 50% Pulse 100% AM @ 1890 Mhz

1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:

±3 kV @ 5 kHz on power ports

±3 kV @ 5 kHz on signal ports

±3 kV @ 5 kHz on communications ports

Surge transient
immunity

IEC 61000-4-5:

±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports

±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports

±2 kV line-earth(CM) on communications ports

Conducted RF
immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications

Certification (when
product is marked)

(1)

(1)

See the Product Certification link at

http://www.ab.com

for Declaration of Conformity, Certificates, and other

certification details.

Value

c-UR-us

UL Recognized Component Industrial Control Equipment, certified for US and

Canada. See UL File E322657.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

EtherNet/IP

ODVA conformance tested to EtherNet/IP specifications.

KC

Korean Registration of Broadcasting and Communications Equipment,

compliant with:

Article 58-2 of Radio Waves Act, Clause 3

Environmental Specifications

Attribute

Value

Advertising