Mold Pressure Module
Publication 1746-5.13 July 1998
Select the hex-equivalent value from the following table
(
Important:
Before operating the module for the first time, you must
download the G file to the module. Do this by downloading your ladder
file, even if it contains no rungs. The SLC processor must be in Program
mode for a download.
Bits 07-00
07-05
04
03
02-00
Chnl 1 Data Source
Chnl 2 Data Source
Hex
0
0
0
0
sensor
sensor
xx00
0
1
SLC output image tbl
sensor
xx08
1
0
sensor
SLC output image tbl
xx10
1
1
SLC output image tbl
SLC output image tbl
xx18
Bits 11-08
11
10
09
08
Triggers
T4 turns alarms OFF?
Alarms OFF when T4
Hex
0
0
0
0
ON
NO
n/a
x0xx
0
0
1
0
OFF
NO
n/a
x2xx
0
1
0
0
ON
YES
Goes ON at mold close
x4xx
0
1
1
0
OFF
YES
Goes OFF at mold open
x6xx
1
0
0
0
ON
NO
n/a
x8xx
1
0
1
0
OFF
NO
n/a
xAxx
1
1
0
0
ON
YES
Goes ON at mold close
xCxx
1
1
1
0
OFF
YES
Goes OFF at mold open
xExx
Bits 15-12
15
14
13
12
Chnl 1 sensor level
Chnl 2 sensor level
Alarms
Hex
1
0
0
0
low
low
ON
8xxx
1
0
0
1
high
low
ON
9xxx
1
0
1
0
low
high
ON
Axxx
1
0
1
1
high
high
ON
Bxxx
1
1
0
0
low
low
OFF
Cxxx
1
1
0
1
high
low
OFF
Dxxx
1
1
1
0
low
high
OFF
Exxx
1
1
1
1
high
high
OFF
Fxxx