Compact™ 16-Point 100 to 240V ac Solid State Output Module 15

Publication 1769-IN061A-EN-P - December 2001

Output Specifications

Specification

1769-OA16

Voltage Category

120 to 240V ac

Operating Voltage Range

85V ac to 265V ac at 47 to 63 Hz

Number of Outputs

16

Bus Current Draw (max.)

225 mA at +5V dc line (1.125W)

Heat Dissipation

4.9 Total Watts
(The Watts per point, plus the minimum Watts, with all
points energized.)

Signal Delay (max.) – resistive load

(1)

(1)

Turn On Type - Triac outputs turn ON and OFF at ac line zero cross.

turn-on = 1/2 cycle
turn-off = 1/2 cycle

Off-State Leakage (max.)

(2)

(2)

Recommended Loading Resistor - To limit the effects of leakage current through solid state outputs, a loading resistor can
be connected in parallel with your load. For 120V ac operation, use a 15K

, 2W resistor. For 240V ac operation use a

15K

, 5W resistor.

2.0 mA at 132V ac
2.5 mA at 265V ac

On-State Current (min.)

10.0 mA

On-State Voltage Drop (max.)

1.5V ac at 0.5 A

Continuous Current per Point (max.)
See the derating graphs on page 16.

0.25A at 60°C (140°F)
0.5A at 30°C (86°F)

Continuous Current per Common

2.0 A at 60°C (140°F)
4.0 A at 30°C (86°F)

Continuous Current Per Module (max.)
See the derating graphs on page 16.

4.0 A at 60°C (140°F)
8.0 A at 30°C (86°F)

Surge Current (max.)

(3)

(3)

Surge Suppression - Connecting surge suppressors across your external load will extend the life of the triac outputs. For
additional details, refer to

Industrial Automation Wiring and Grounding Guidelines

, Allen-Bradley publication 1770-4.1.

5.0A (Repeatability is once every 2 seconds for a duration
of 25 msec.)

Power Supply Distance Rating

8 (The module may not be more than 8 modules away from
the power supply.)

Output Point to Bus Isolation

Verified by one of the following dielectric tests: 1836V ac
for 1 sec. or 2596V dc for 1 sec.
265V ac working voltage (IEC Class 2 reinforced insulation)

Isolated Groups

Group 1: outputs 0 to 7
Group 2: outputs 8 to 15

Output Group to Output Group Isolation

Verified by one of the following dielectric tests: 1836V ac
for 1 sec. or 2596V dc for 1 sec.
265V ac working voltage (basic insulation)
150V ac working voltage (IEC Class 2 reinforced insulation)

Vendor I.D. Code

1

Product Type Code

7

Product Code

93