6 Compact™ 16-Point 100 to 240V ac Solid State Output Module

Publication 1769-IN061A-EN-P - December 2001

Panel Mounting Using the Dimensional Template

Locate holes every 17.5 mm (0.689 in.) to allow for a mix of single-wide
(e.g. 1769-IQ16) and one-and-a-half-wide modules (e.g. 1769-OA16).

Panel Mounting Procedure Using Modules as a Template

The following procedure allows you to use the assembled modules as a template
for drilling holes in the panel. If you have sophisticated panel mounting equipment,
you can use the dimensional template provided on page 6. Due to module
mounting hole tolerance, it is important to follow these procedures:

1. On a clean work surface, assemble no more than three modules.

2. Using the assembled modules as a template, carefully mark the center of all

module-mounting holes on the panel.

3. Return the assembled modules to the clean work surface, including any

previously mounted modules.

4. Drill and tap the mounting holes for the recommended M4 or #8 screw.

5. Place the modules back on the panel, and check for proper hole alignment.

6. Attach the modules to the panel using the mounting screws.

7. Repeat steps 1 to 6 for any remaining modules.

TIP

If mounting more modules, mount only the last one of
this group and put the others aside. This reduces
remounting time during drilling and tapping of the next
group.

H

os

t Controller

Spacing for single-wide modules 35 mm (1.378 in.)

Refer to host controller documentation for this dimension.

Note: Overall hole spacing
tolerance: ±0.4 mm (0.016 in.).

Spacing for one-and-a half-wide modules 52.5 mm (2.067 in.)