Chapter 1 Store and load a project by using a memory card
5. At the bottom of the Image in Nonvolatile Memory area, click Load -->.
A dialog box asks you to confirm the load.
6. To load the project from the memory card, click Yes.
The table describes the events that occur for these memory cards.
Logix Designer application goes offline.
When the load is finished, you remain offline.
If using
And the load
Then the OK status indicators display
CompactFlash Card
Does not include
firmware
Solid red> solid green
Includes firmware
Flashing red> solid red> solid green
SD Card
Does not include
firmware
OK status indicator is solid green; SD status indicator flashes
green.
Status Display shows LOAD. See the illustration.
Includes firmware
OK status indicator flashes red; SD status indicator flashes
green.
Status Display shows UPDT. See the illustration.
20