Din rail mounting – Rockwell Automation 1769-SDN Compact I/O DeviceNet Scanner Module Installation Instructions User Manual

Page 12

Advertising
background image

12 Compact I/O DeviceNet Scanner Module

Publication 1769-IN060C-EN-P - May 2002

Panel Mounting Procedure Using Modules as a Template

The following procedure allows you to use the assembled modules as a template
for drilling holes in the panel. Due to module mounting hole tolerance, it is
important to follow these procedures:

1. On a clean work surface, assemble no more than three modules.

2. Using the assembled modules as a template, carefully mark the center of all

module-mounting holes on the panel.

3. Return the assembled modules to the clean work surface, including any

previously mounted modules.

4. Drill and tap the mounting holes for the recommended M4 or #8 screw.

5. Place the modules back on the panel, and check for proper hole alignment.

6. Attach the modules to the panel using the mounting screws.

7. Repeat steps 1 to 6 for any remaining modules.

DIN Rail Mounting

The module can be mounted using the following DIN rails: 35 x 7.5 mm (EN 50 022
- 35 x 7.5) or 35 x 15 mm (EN 50 022 - 35 x 15).

Before mounting the module on a DIN rail, close the DIN rail latches. Press the DIN
rail mounting area of the module against the DIN rail. The latches will momentarily
open and lock into place. DIN rail mounting dimensions are shown below.

A

B

C

Dimension

Height

A

118 mm
(4.65 in.)

B

59 mm
(2.325 in.)

C

59 mm
(2.325 in.)

Advertising