Compact I/O DeviceNet Scanner Module 15

Publication 1769-IN060C-EN-P - May 2002

DeviceNet Wiring

1. Connect the DeviceNet cable to the removable connector as shown.

2. Insert the removable female connector into the mating male connector on

the DeviceNet scanner module.

3. Screw the removable connector to the scanner case with the upper and

lower mounting screws. Screw torque is 0.6 to 0.7 Nm (5 to 6 in-lbs).

Scanner Module Power-Up

When power is applied via the Compact I/O bus, the scanner module goes through
a self test sequence. Upon successful completion of the self test, the scanner is
ready to communicate.

The default scanner settings are:

baud rate = 125K

node address = 63

Use your configuration software to change the baud rate and node address.

IMPORTANT

If the 1769-SDN is the first or last device connected to the
DeviceNet network trunkline, be sure to add a termination resistor
(120

1%

¼W resistor, Allen-Bradley part number 1485A-C2)

across the Blue (CAN Low) and White (CAN High) wires.

DeviceNet Connector

Connect

(1)

To

Red Wire

V+

White Wire

CAN High

Bare Wire

Shield

Blue Wire

CAN Low

Black Wire

V-

Grounding Screw
Use #14 AWG wire
to connect to panel
ground.