Rockwell Automation 1732E-IR4IM12R ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input User Manual

Page 19

Advertising
background image

1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules 19

Publication 1732E-IN005B-EN-E - September 2012

Thermocouple types

Type

Material

Temperature

Range °C (°F)

Voltage

Range (mV)

B

Pt /30% Rh vs. Pt/5% Rh

40…1820

(104…3308)

0…13.820

C

W/5% Re vs. W/26% Re

0…2320

(32…4208)

0…37.107

E

Ni/Cr vs. Cu/Ni

-270…1000

(-454…1832)

-9.835…76.373

J

Ni/Cr vs. Cu/Ni

-210…1200

(-346…2192)

-8.095…69.553

K

Ni/Cr vs. Ni/Al

-270…1372

(-454…2501.6)

-6.458…54.886

N

Ni/14.2%Cr/1.4%Si vs.
Ni/4.4%Si/0.1%Mg

-270…1300

(-454…2372)

-4.345…47.513

R

Pt/13%Rh vs. Pt

-50…1768

(-58…3214.4)

-0.226…21.101

S

Pt/10%Rh vs. Pt

-50…1768

(-58…3214.4)

-0.236…18.693

T

Cu vs. Cu/Ni

-270…400

(-454…752)

-6.258…20.872

CJC Terminal Chamber
recommended

Rockwell Automation 871A-TS4CJC-DM, 871A-TR4CJC-DM

Cold junction
compensation range

0…70 °C (32…158 °F) for 302 type thermistors

Cold junction
compensation modes

Average Selected, Channel Independent, and CJC Offset

(For more information, see the User Manual, publication

1732E-UM004

)

Thermistor types
supported

Thermometrics MF65F302V/W or DC95F302V/W

Input voltage range

±78.125 mV

0…78.125 mV

Accuracy

0.1% Full Scale @ 25 °C (77 °F)

Accuracy drift with
temperature

30 ppm % Full Scale /°C @ 25 °C (77 °F)

Calibration

Factory calibrated. Calibration is also supported through RSLogix 5000.

Input Specifications – 1732E-IT4IM12R

Attributes

Value

Advertising