20 1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules
Publication 1732E-IN005B-EN-E - September 2012
Common mode 
rejection rate
120 dB @ 50/60 Hz
Normal mode rejection 
rate
100 dB @ 50/60 Hz
Sample Rate Filters
(1)
50 Hz
60 Hz
250 Hz
500 Hz
(1)
Sample Rate/Notch Filter Frequency, selectable per channel.
Input Specifications – 1732E-IR4IM12R
Attributes
Value
Number of inputs
4, isolated
Resolution, min
16 bits
Data format
16-bit sign magnitude
Sensors supported
100…200
 =0.00385/0.003916 Pt RTD 
100/120
 Ni RTD 
10
 Cu  =0.00427 RTD
Sensor Types
100
 Pt 385
200
 Pt 385
100
 Pt 3916
200
 Pt 3916
10
 Cu 427
120
 Ni 672
100
 Ni 618
120
 Ni 618
Input Specifications – 1732E-IT4IM12R