Rockwell Automation 1732E-IR4IM12R ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input User Manual

Page 20

Advertising
background image

20 1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules

Publication 1732E-IN005B-EN-E - September 2012

Common mode
rejection rate

120 dB @ 50/60 Hz

Normal mode rejection
rate

100 dB @ 50/60 Hz

Sample Rate Filters

(1)

50 Hz

60 Hz

250 Hz

500 Hz

(1)

Sample Rate/Notch Filter Frequency, selectable per channel.

Input Specifications – 1732E-IR4IM12R

Attributes

Value

Number of inputs

4, isolated

Resolution, min

16 bits

Data format

16-bit sign magnitude

Sensors supported

100…200

 =0.00385/0.003916 Pt RTD 

100/120

 Ni RTD 

10

 Cu  =0.00427 RTD

Sensor Types

100

 Pt 385

200

 Pt 385

100

 Pt 3916

200

 Pt 3916

10

 Cu 427

120

 Ni 672

100

 Ni 618

120

 Ni 618

Input Specifications – 1732E-IT4IM12R

Attributes

Value

Advertising