Specifications – Rockwell Automation 1771-OQ16/C Isolated Output Module Installation Instr User Manual

Page 13

Advertising
background image

DC (24V) Isolated Output Module

13

Publication 1771ĆIN057B-EN-P - November 2002

Outputs per Module

16

Module Location

1771ĆA1B thru Ć A1B or later I/O Chassis

Voltage Rating

10 to 32V dc

Maximum Output Current

2.0A per output; 32.0A maximum per module at 0-45

o

C;

Derate linearly to 1.5A per output, 24A maximum per module at 60

o

C -

See derating curve.

Minimum Output Current

5mA

OnĆstate Voltage Drop (maximum) 0.34A per output at 2A
OffĆstate Leakage Current

(maximum)

0.5mA per output @ 32V dc, 25

o

C

Surge Current (maximum)

4A for 10ms per output., repeatable every 2 sec.

Power Rating

0.68W per output (maximum) @ 2A

Output Signal Delay Off to On

On to Off

100μs (max);

300μs (max)

Power Dissipation

13.0 Watts (max); 2.0 Watts (min)

Thermal Dissipation

44.3 BTU/hr (max); 6.8 BTU/hr (min)

Adjacent Slot Power Dissipation

10.0 Watts

Backplane Current

400mA maximum

Isolation Voltage

Testedfor 1s at 1500V channelĆtoĆchannel,

1500V channel to backplane

Maximum Cable Length

1000 ft (304.8 m)

Conductors Wire Size

Category

14 to 22 gauge (2.5mm

2

to 0.25mm

2

) strandedor solidcopper wire rated

at 60

o

C or greater

1, 2

3/64 inch insulation maximum

2

3

Environmental Conditions

Operating

Temperature

IEC 60068-2-1 (Test Ad, Operating Cold)

IEC 60068-2-2 (Test Bd, Operating Dry Heat)

IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

32 to 140°F (0

o

to 60

o

C) See derating curve.

Storage Temperature

IEC 60068-2-1 (Test Ab, Unpackaged, Nonoperating Cold)

IEC 60068-2-2 (Test Bb, Unpackaged, Nonoperating Dry Heat)

IEC 60068-2-14 (Test Na, Unpackaged, Nonoperating Thermal Shock)

-40 to 185°F (-40 to 85

o

C)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged, Nonoperating Damp Heat)

5 to 95%, noncondensing

Shock

Operating

Nonoperating

IEC 60068-2-27 (Test Ea, UnpackagedShock)

30g

50g

Vibration

IEC 60068-2-6 (Test Fc, Operating)

2g @ 10-500Hz

ESD Immunity

IEC 61000-4-2

4kV indirect discharges

Radiated RF Immunity

IEC 61000-4-3

10V/m, with 1kHz sine-wave 80% AM from 30MHz to 1000MHz

EFT/B Immunity

IEC 61000-4-4

+1kV @ 5kHz on signal ports

Surge Transient Immunity

IEC 61000-4-5

+1kV line-line (DM) and+2kV line-earth (CM) on signal ports

Specifications continued on next page.

Specifications

Advertising