European Hazardous Location Approval

The following adapters are European Zone 2 approved:
1794-ADN and -ADNK series C adapters.

North American Hazardous Location Approval

The following adapter is North American Hazardous Location approved:
1794-ADN Series C and 1794-ADNK Series C adapters.

DeviceNet Adapter, Cat. No. 1794-ADN/C and 1794-ADNK/C

Installing Your DeviceNet Adapter Module

ATTENTION

To comply with the CE Low Voltage Directive (LVD), this equipment
must be powered from a source compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage
(PELV).

ATTENTION

To comply with UL restrictions, this equipment must be powered
from a source compliant with the following:
Class 2 or Limited Voltage/Current.

ATTENTION

Preventing Electrostatic Discharge

This equipment is sensitive to electrostatic discharge, which can
cause internal damage and affect normal operation. Follow these
guidelines when you handle this equipment:

 Touch a grounded object to discharge potential static.
 Wear an approved grounding wriststrap.
 Do not touch connectors or pins on component boards.

 Do not touch circuit components inside the equipment.
 If available, use a static-safe workstation.

European Zone 2 Certification (The following applies when the product
bears the Ex Marking)

This equipment is intended for use in potentially explosive atmospheres as defined
by European Union Directive 94/9/EC and has been found to comply with the
Essential Health and Safety Requirements relating to the design and construction of
Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres,
given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by
compliance with EN 60079-15 and EN 60079-0.

WARNING

Observe the following additional Zone 2 certification
requirements.

 This equipment is not resistant to sunlight or other sources

of UV radiation.

 This equipment must be installed in an enclosure providing

at least IP54 protection when applied in Zone 2
environments.

 This equipment shall be used within its specified ratings

defined by Rockwell Automation.

 Provision shall be made to prevent the rated voltage from

being exceeded by transient disturbances of more than 40%
when applied in Zone 2 environments.

 This equipment must be used only with ATEX certified

Rockwell Automation Terminal Bases.

 Secure any external connections that mate to this equipment

by using screws, sliding latches, threaded connectors, or
other means provided with this product.

 Do not disconnect equipment unless power has been

removed or the area is known to be nonhazardous.

The following information applies when
operating this equipment in hazardous
locations:

Informations sur l’utilisation de cet
équipement en environnements dangereux:

Products marked "CL I, DIV 2, GP A, B, C, D"
are suitable for use in Class I Division 2
Groups A, B, C, D, Hazardous Locations and
nonhazardous locations only. Each product is
supplied with markings on the rating
nameplate indicating the hazardous location
temperature code. When combining products
within a system, the most adverse
temperature code (lowest "T" number) may be
used to help determine the overall
temperature code of the system.
Combinations of equipment in your system
are subject to investigation by the local
Authority Having Jurisdiction at the time of
installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
conviennent qu'à une utilisation en
environnements de Classe I Division 2 Groupes A,
B, C, D dangereux et non dangereux. Chaque
produit est livré avec des marquages sur sa plaque
d'identification qui indiquent le code de
température pour les environnements dangereux.
Lorsque plusieurs produits sont combinés dans un
système, le code de température le plus
défavorable (code de température le plus faible)
peut être utilisé pour déterminer le code de
température global du système. Les combinaisons
d'équipements dans le système sont sujettes à
inspection par les autorités locales qualifiées au
moment de l'installation.

WARNING

EXPLOSION HAZARD

• Do not disconnect

equipment unless power
has been removed or the
area is known to be
nonhazardous.

• Do not disconnect

connections to this
equipment unless power
has been removed or the
area is known to be
nonhazardous. Secure any
external connections that
mate to this equipment by
using screws, sliding
latches, threaded
connectors, or other
means provided with this
product.

• Substitution of

components may impair
suitability for Class I,
Division 2.

• If this product contains

batteries, they must only
be changed in an area
known to be
nonhazardous.

AVERTISSEMENT

RISQUE D’EXPLOSION

• Couper le courant ou

s'assurer que
l'environnement est classé
non dangereux avant de
débrancher l'équipement.

• Couper le courant ou

s'assurer que
l'environnement est classé
non dangereux avant de
débrancher les connecteurs.
Fixer tous les connecteurs
externes reliés à cet
équipement à l'aide de vis,
loquets coulissants,
connecteurs filetés ou autres
moyens fournis avec ce
produit.

• La substitution de

composants peut rendre cet
équipement inadapté à une
utilisation en environnement
de Classe I, Division 2.

• S'assurer que

l'environnement est classé
non dangereux avant de
changer les piles.

Component Identification

1

DeviceNet Adapter Module

5

DeviceNet Node selection
thumbwheel switches

2

Indicators

6

+24V DC connections

3

Wiring label

7

24V common connections

4

DeviceNet network cable
(plug-in, screw-secured)

8

Flexbus connector

1

2

3

4

6

7

8

5