Publication 1794-IN099C-EN-P - May 2010

Supply voltage

Power supply: 19.2...31.2V DC, 400 mA
DeviceNet power: 24V DC, 90 mA, Class 2
Flexbus output: 5V DC, 640 mA

Input voltage
rating

24V DC nom
19.2V to 31.2 V DC (includes 5% AC ripple)

Current draw

400 mA maximum; 300 mA at 24V DC

Communication
rate

125 KB
250 KB
500 KB

Indicators

Power - on/off
ModNet status - red/green
I/O status - red/green

Flexbus output
current

640 mA max. @ 5V DC

Isolation
voltage

50V (continuous), Basic Insulation Type
Type tested at 1930V DC for 60 s, power to Flexbus, power to
DeviceNet, and DeviceNet to Flexbus

Power
dissipation

7.6W maximum @ 19.2V DC

Thermal
dissipation

26 BTU/hr @ 19.2V DC

DeviceNet
power
requirements

24V DC (

±

4%) at 90 mA max

Dimensions
(HxWxD)

87 x 68 x 69 mm (3.4 x 2.7 x 2.7 in)

Weight

195.5 g (6.9 oz)

Enclosure type
rating

None (open-style)

Wire size

Power connections:

0.33... 3.3 mm² (22...12 AWG) solid or stranded copper wire
rated at 75 °C (167 °F ) or greater 1.2 mm (3/64 in.) insulation
max

Wiring

category

(1)

1 - on power ports
2 - on communications ports

Terminal screw
torque

0.8 Nm (7 lb-in)

North American
temp code

T4

IEC temp code

T4

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication

1770-4.1.

Environmental

Attribute

Value

Operating
temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…70 °C (-4…158 °F)

Surrounding
air
temperature,
max

70 °C (158 °F)

Non-operating
temperature

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal
Shock):
-40…85 °C (-40…185 °F)

Relative
humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz

General

Operating
shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g

Non-operating
shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g

Emissions

CISPR 11:
Group 1, Class A (with appropriate enclosure)

ESD immunity

IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges

Radiated RF
immunity

IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B
immunity

IEC 61000-4-4:
±4 kV at 5 kHz on power ports
±4 kV at 5 kHz on communications ports

Surge
transient
immunity

IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports
±2 kV line-earth(CM) on communications ports

Conducted RF
immunity

IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications (when product is marked)

(1)

(1)

See the Product Certification link at

http://www.ab.com

for Declaration of Conformity, Certificates, and

other certification details.

Attribute

Value

c-UL-us

UL Listed Industrial Control Equipment, certified for US and

Canada. See UL File E65584.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous

Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with:

EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
EN 60079-0; General Requirements
II 3 G Ex nA IIC T4 X