1785-5.19 - January 1999

Optical Transceiver

3

Installation

Fiber Optic Connection

Two BFOC sockets are available for connecting the 1785-TR10BF
transceiver to a fiber optic segment. One connection is used for transmitting
and one for receiving data over the fiber optic cable.

The maximum length of the fiber optic segment is

2000 m for 50/125 fiber

3000 m for 62.5/125 fiber

Power Supply

The operating voltage (+12 V) is taken from the connected device via the
15-pin sub-D socket of the AUI interface.

SQE Test Setting

The slide switch on the top of the transceiver case is used to activate and
deactivate the SQE test. Before placing the transceiver in operation, you
should check to see whether the connected device requires the SQE test to
be on or off. As delivered from the factory, the SQE test is on.

Connecting Devices

For Additional Information

For standards information, go to

http://www.ieee.org/

. To download a .PDF

copy of this publication, go to

http://www.theautomationbookstore.com/

.

Connecting two devices

PC

PLC5E

1785-TR10BF

1785-TR10BF

Fiber optic cable 2000 meters (50/125 microns)

3000 meters (62.5/125 microns) max.

Connecting to
a fiber optic interface hub

PLC5E

Hub

1785-TR10BF

1785-TR10BF

Fiber optic cable 2000 meters (50/125 microns)

3000 meters (62.5/125 microns) max.