Connection capabilities
Transceiver interface

Fiber optic interface


plugged directly on to the AUI interface of connected device
or connected by an AUI cable (50 m max. length)
Fiber optic cable segment maximum
2000 m (50/125 microns) or 3000 m (62.5/125 microns) long

Connections with pin assignments
Transceiver interface
(15-pin sub-D plug)



Fiber optic interface


Input:DO-A: pin 3; DO-B: pin 10
Output:DI-A: pin 5; DI-B: pin 12
Collision detect:CI-A: pin 2; CI-B: pin 9
Power:GND: pin 6; +12 V: pin 13
Shielding:pin 1, 4, 8, 11, 14
2 x IEC 874-10 BFOC/2.5 sockets

Displays

* green LED: LINK (link status)

on - fiber optic connection OK

* yellow LED: RX (Rx data)

on - data being received over fiber optic cable link

* red LED: CD (collision detect)

brief flash – data collision
continuously on – jabber control active

* yellow LED: TX (Tx data)

on - data being transmitted through fiber optic cable link

* green LED: P (power)

on – supply voltage present

Conductors/Wire Size/Category

Category 1

1

Agency Certification
(when product is marked)

Information Technology Equipment

Industrial Control Equipment

Class I, Div. 2, Groups A, B. C, D
Hazardous Location

EN 50082-1, 2

EN 55022, Radiated Emission Class B

EN 60950

FCC Part 15, SubPart B

1

Refer to the Industrial Automation Wiring and Grounding Guidelines for Noise Immunity, publication 1770-4.1.