Wiring

This module is available with 2 styles of terminations: 1793-IB4 -
screw-cage and 1793-IB4S - spring-clamp. Refer to the wiring figure
below.

1.

Connect individual sensor signal input leads to terminals 2 through 5
on row A (channels 0 thru 3 respectively).

2.

Connect sensor supply lead to +24V dc (terminals 1, 6, 9, or 14).
(Terminals 1, 6, 8, 9, 14 and 15 are connected internally to +24V dc.)

3.

For 3-wire sensors only: Connect associated common to terminals 10
through 13 on row B.

4.

Connect +24V dc voltage to terminal 8 on row B.

5.

Connect 24V dc common to terminal 0 on row A.

6.

If daisy-chaining + voltage from this module to the next Integra
module, connect a jumper from terminal 15 to terminal 8 on the next
FLEX Integra module.

7.

If daisy-chaining 24V dc common from this module to the next FLEX
Integra module, connect a jumper from terminal 7 on this module to
terminal 0 on the next Integra module.

.

!

ATTENTION:

Total current draw through the module’s

(+) voltage terminals is limited to 10A. Separate power
connections to the module may be required.

0

1

2

3

4

5

6

7

8

9

10

11

A

B

13

14

15

12

41378

C

V I

I

I

I

C

V

C

C

V

V

C

C

V

V

Ch 0

Ch 1

Ch 2 Ch 3

0

1 2 3 4 5 6

7

8 9 10 11 12 13 14 15

A

B

41379

C V I

I

I I

C

V

C C

V

V

C C

V

V

Ch 0 Ch 1 Ch 2 Ch 3

1793-IB4

1793-IB4S

Where: C = common, V = +24V dc power, I = input

Advertising
This manual is related to the following products: