Memory Mapping

Setting the Input Delay Time

You can select the input delay time (DT) for channels 00 thru 03. Select the
input delay time by setting the corresponding bits in the output image table
(complementary word) for the module.

For example, to set a delay time of 4ms for an input module at address rack
1, module group 0, set bits 02, 01 and 00 as shown below.

Input Delay Times

Bit/
Word

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Read

Reserved

I3

I2

I1

I0

Write

Reserved

DT 00-03

Where: I = Input

DT = delay time - refer to “Setting the Input Delay Time”

02

01

00

Filter Time for Inputs 00-03

Selected
Filter Time

0

0

0

Filter Time 0 (default)

512

μs

0

0

1

Filter Time 1

1ms

0

1

0

Filter Time 2

2ms

0

1

1

Filter Time 3

4ms

1

0

0

Filter Time 4

8ms

1

0

1

Filter Time 5

16ms

1

1

0

Filter Time 6

32ms

1

1

1

Filter Time 7

64ms

15 14 13 12

11 10 09 08 07 06 05 04 03 02 01 00

0

1

1

= 3 Octal or 3 decimal

Write delay time on system startup.

Write DT to complement

of input module.

Fill File
Source

Destination
Length

3

#O:010

1

I:000

00

FLL

O:010

Dec.

41335