Hart command 1 – Rockwell Automation 1770,D17706.5.21 SMART TRANSMITTER TOOLKI User Manual
Page 40

HART Command Data Table Layouts
Appendix A
A-5
Standard Outputs
Integer
Word 30
STT Subroutine Status Word
Word 31
STT Subroutine Error Code
Word 32
Smart Transmitter Interface Status Word
Word 33
Smart Transmitter Interface Error Code
Word 34
HART ProtocolĆCommunication Error Code
Word 35
HART Command Response Summary Error Code
Word 36
HART Field Device Error Code
CommandĆspecific Outputs
Integer
Word 40
Primary Variable Unit Code
FloatingĆpoint
Word 10
Primary Variable
Data Table Report PLC-5/25 Addr 31 Data Table File N10:0
Address 0 1 2 3 4 5 6 7 8 9
N10:0 4 6 3 0 16 1 9858 269 12807 0
N10:10 0 0 0 0 0 0 0 0 0 0
N10:20 0 0 0 0 0 0 0 0 0 0
N10:30 4 0 128 0 0 0 0 0 0 0
N10:40 32 0 0 0 0 0 0 0 0 0
N10:50 0 0 0 0 0 0 0 0 0 0
This integer word is a commandĆspecific
output that contains the unit code for the
primary variable (see page BĆ5).
These seven integer words are the standard outputs
that contain the status of the communications with
the HART field device (see page 3Ć6).
Data Table Report PLC-5/25 Addr 31 Data Table File F11:0
Address 0 1 2 3 4
F11:0 0 0 0 0 0
F11:5 0 0 0 0 0
F11:10 20.58 0 0 0 0
F11:15 0 0 0 0 0
This floatingĆpoint word is a commandĆspecific
output that contains the primary variable.
HART Command 1
Read Primary Variable