Ać12, Hart command 43 – Rockwell Automation 1770,D17706.5.21 SMART TRANSMITTER TOOLKI User Manual
Page 47

HART Command Data Table Layouts
Appendix A
A-12
Use this command to trim the primary variable so that it reads zero with
the existing process applied to the HART field device. The resulting offset
must be within the limits defined by each device.
Standard Inputs
Integer
Word 0
I/O Rack Number of 1770ĆHT1
Word 1
I/O Group Number of 1770ĆHT1
Word 2
Channel Number of HART field device
Word 3
Polling Address of HART field device
Word 4
Smart Transmitter Interface Command Number 16 (decimal)
Word 5
HART Command Number 43
CommandĆspecific Inputs
Integer
Words 6 Ć 8
HART Address from HART Command 0
Data Table Report PLC-5/25 Addr 31 Data Table File N10:0
Address 0 1 2 3 4 5 6 7 8 9
N10:0 4 6 3 0 16 43 9858 269 12807 0
N10:10 0 0 0 0 0 0 0 0 0 0
N10:20 0 0 0 0 0 0 0 0 0 0
N10:30 0 0 0 0 0 0 0 0 0 0
N10:40 0 0 0 0 0 0 0 0 0 0
N10:50 0 0 0 0 0 0 0 0 0 0
These six integer words are the
standard inputs that are required for
each HART command (see page 3Ć3).
This is the HART address that is returned
from HART Command 0 (see page AĆ3).
HART Command 43
Set Primary Variable Zero