Specifications – Rockwell Automation 1791R-XXXX CompactBlock RIO User Manual
Page 24

24 CompactBlock Distributed I/O on Remote I/O
Publication 1791R-IN001A-EN-P - February 2002
Specifications
Comm Status Indicator
Indication:
Status:
Off
Communication not established
Green
Communication established
Flashing Green
Processor in Program mode
I/O Status Indicators
Function:
LED Color:
Module
Illumination:
Condition:
Outputs
Each output:
Yellow
None
Yellow
Output not energized
Output energized
Inputs
Each Input:
Yellow
None
Yellow
No valid input
Valid input
Sinking or Sourcing Input Specifications
Inputs per block
groups of 4 or 8
Off-state Voltage
5V dc maximum
On-state Voltage
30V dc @ 40
°
C maximum
25V dc @ 60
°
C maximum
10V dc minimum
Off-state Current
1.5mA minimum
On-state Current
11mA @ 30V dc maximum
2mA @ 10V dc minimum
Sinking or Sourcing Output Specifications
Outputs per block
groups of 4 or 8
On-state Voltage Range
10 - 30V dc
On-state Voltage Drop
0.5V dc @ rated current
On-state Current
0.5A maximum
Off-state Leakage
1.0mA maximum
Module Current (per output)
0.5A maximum
Surge Current - for 10 mS
repeatable every 2 S
1.0A maximum