Rockwell Automation 1794-OW8_OW8K_OW8XT Flex I/O 8 Output Relay Module User Manual
European hazardous location approval
 
Publication 1794-IN019H-EN-P - January 2011
Installation Instructions
FLEX I/O 8 Relay Output Module
Cat. No. 1794-OW8, 1794-OW8K, 1794-OW8XT
(Modules with catalog numbers that end in K are conformally coated to meet 
noxious gas requirements of ISA/ANSI-71.040 1985 Class G3 Environment.)
European Hazardous Location Approval
The following applies when the product bears the Ex Marking.
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical 
equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State 
well Automation sales office or online at
ribes some important differences between solid
state equipment and hard-wired electromechanical devices. Because of this difference, and also 
because of the wide variety of uses for solid state equipment, all persons responsible for applying 
this equipment must satisfy themselves that each intended application of this equipment is 
acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential 
damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of 
the many variables and requirements associated with any particular installation, Rockwell 
Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and 
diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, 
circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of 
Rockwell Automation, Inc. is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an 
explosion in a hazardous environment, which may lead to personal injury or 
death, property damage, or economic loss.
IMPORTANT
Identifies information that is critical for successful application and 
understanding of the product.
ATTENTION
Identifies information about practices or circumstances that can lead to 
personal injury or death, property damage, or economic loss. Attentions help 
you identify a hazard, avoid a hazard, or recognize the consequence
ATTENTION
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial 
environment, in overvoltage Category II applications (as defined in IEC 
60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment 
according to IEC/CISPR 11. Without appropriate precautions, there may be 
difficulties with electromagnetic compatibility in residential and other 
environments due to conducted and radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted 
within an enclosure that is suitably designed for those specific 
environmental conditions that will be present and appropriately designed 
to prevent personal injury resulting from accessibility to live parts. The 
enclosure must have suitable flame-retardant properties to prevent or 
minimize the spread of flame, complying with a flame spread rating of 
5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the 
enclosure must be accessible only by the use of a tool. Subsequent 
sections of this publication may contain additional information regarding 
specific enclosure type ratings that are required to comply with certain 
product safety certifications.
In addition to this publication, see:
•
Industrial Automation Wiring and Grounding Guidelines, publication
itional installation requirements.
•
NEMA Standard 250 and IEC 60529, as applicable, for explanations 
of the degrees of protection provided by enclosures.
ATTENTION
FLEX I/O is grounded through the DIN rail to chassis ground. Use zinc 
plated yellow-chromate steel DIN rail to assure proper grounding. The use 
of other DIN rail materials (for example, aluminum or plastic) that can 
corrode, oxidize, or are poor conductors, can result in improper or 
intermittent grounding. Secure DIN rail to mounting surface approximately 
every 200 mm (7.8 in.) and use end-anchors appropriately.
ATTENTION
Preventing Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause 
internal damage and affect normal operation. Follow these guidelines 
when you handle this equipment:
•
Touch a grounded object to discharge potential static.
•
Wear an approved grounding wriststrap.
•
Do not touch connectors or pins on component boards.
•
Do not touch circuit components inside the equipment.
•
Use a static-safe workstation, if available.
•
Store the equipment in appropriate static-safe packaging when 
not in use.
WARNING
If you connect or disconnect wiring while the field-side power is on, an 
electrical arc can occur. This could cause an explosion in hazardous location 
installations. Be sure that power is removed or the area is nonhazardous 
before proceeding.
ATTENTION
Personnel responsible for the application of safety-related programmable 
electronic systems (PES) shall be aware of the safety requirements in the 
application of the system and shall be trained in using the system.
ATTENTION
Do not remove or replace a Terminal Base unit while power is applied. 
Interruption of the backplane can result in unintentional operation or 
machine motion.
ATTENTION
To comply with the CE Low Voltage Directive (LVD), this equipment must 
be powered from a source compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
This equipment is intended for use in potentially explosive atmospheres as defined by European 
Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety 
Requirements relating to the design and construction of Category 3 equipment intended for use 
in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by 
compliance with EN 60079-15 and EN 60079-0.
Document Outline
- 1794-IN019H-EN-P Flex I/O 8 Relay Output Module Installation Instructions
- European Hazardous Location Approval
- North American Hazardous Location Approval
- Installing Your Relay Output Module
- Simplified Schematic of the Relay Module
- Working Voltage and Isolation Voltage Ratings
- Wiring to a 1794-TB2, 1794-TB3 or 1794-TB3S Terminal Base Unit
- Wiring to a 1794-TBN or 1794-TBNF Terminal Base Unit
- Installing or Changing a Fuse in the 1794-TBNF
 
- Back Page