Installing or changing a fuse in the 1794-tbnf – Rockwell Automation 1794-OW8_OW8K_OW8XT Flex I/O 8 Output Relay Module User Manual

Page 4

Advertising
background image

4

Publication 1794-IN019H-EN-P - January 2011

Installing or Changing a Fuse in the 1794-TBNF

This terminal base unit has fuse holders for 5 x 20 mm fuses on each of the 8
even-numbered I/O terminals 014 (row B). To install or change a fuse:

1.

Press the fuse holder down toward the terminal strip.

2.

If replacing a fuse, remove the fuse from the fuse holder.

3.

Insert a known good 5 x 20 mm fuse (Littelfuse pt. no. 239003, 3.0 A,
250V AC slow-blow) into the fuse holder.

4.

Replace the fuse holder by rotating the fuse holder back to vertical until it
snaps into the locked position.

Wiring Connections for the 1794-OW8, 1794-OW8K, 1794-OW8XT

Output
Channel

1794-TB2, 1794-TB3, 1794-TB3S

1794-TBN, 1794-TBNF

Output Terminal

Output Terminal

0

A-0

B-0

A-1

C-1

1

A-2

B-2

A-3

C-3

2

A-4

B-4

A-5

C-5

3

A-6

B-6

A-7

C-7

4

A-8

B-8

A-9

C-9

5

A-10

B-10

A-11

C-11

6

A-12

B-12

A-13

C-13

7

A-14

B-14

A-15

C-15

A-(even) = one contact of the relay

A-(odd) = the other contact of the relay

B-(even) = one contact of the relay

C-(odd) = the other contact of the relay

+24V DC

C-34…C-51 (1794-TB3, 1794-TB3S)
C-34 and C-51 (1794-TB2)

C-34 and C- 51

-24V DC
(RET)

B- 16…B-33

B-16 and B-33

Image Table Memory Map

Dec.

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Oct.

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Read Word

Not used - reserved

Write Word

Not used - set to 0

O7 O6 O5 O4 O3 O2 O1 O0

Where:

O = Output number (O0 corresponds to output 0, O1 corresponds to output 1,
and so on)

When bit = 0, output 0 is off; when bit=1, output 0 is on.

WARNING

The 1794-TBNF and 1794-TBNFK are not approved for use in Class I
Division 2 applications.

General Specifications

Attribute

Value

Outputs per module

1 group of 8 Form A isolated (normally open)

electromechanical relays

Module location

Mounts on 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TBN and 1794-TBNF
Terminal Base Units.

When using 1794-TBNF terminal base unit, use 3.0 A, 250V AC slow-blow
fuses (Littelfuse pt. no. 239003)

Off-State leakage

current (max at 240V AC)

1.0 mA through snubber circuit

Minimum contact load

100

μ

A @ 100 mV DC

Flexbus current

5V DC, 35 mA

Supply voltage

24V DC, 125 mA (1794-OW8, 1794-OW8K)

19.2...31.2V DC, 126 mA (1794-OW8XT)

Relay Contact

250V AC, 2 A, 50/60Hz, Resistive;

120/240V AC, 50/60Hz,1800V A Make, 180V A Break;

5…30V DC, 2 A, Resistive;

Pilot Duty Rating

R150, 5...30V DC, 28V A not to exceed 1 A below 28V DC

Output signal delay

OFF to ON

10 ms max (time from valid output on signal to relay energization by
module)

ON to OFF

10 ms max (time from valid output off signal to relay deenergization by
module)

Initial contact resistance

30 m

Ω

Switching frequency

1 operation/3 s (0.3Hz at rated load) max

Bounce time

1.2 ms (mean)

Expected life of

electrical contacts

100,000 operations, min @ rated loads

Thermal dissipation

18.8 BTU/hr max

Power dissipation

5.5 W

Isolation voltage

250V (continuous), Basic Insulation Type, relay to relay, relay to backplane,
and relay to power

50V (continuous), Basic Insulation Type, power to backplane

Type tested at 1500V AC for 60 s, relay to relay, all combinations.

Type tested at 3250V DC for 60 s, relay to backplane and relay to power

Type tested at 720V DC for 60 s, power to backplane.

Fusing

Fusing of outputs is recommended. Use 3.0 A, 250V AC slow-blow fuses
(Littelfuse pt. no. 239003).

Indicators

8 yellow status indicators

Keyswitch position

9

Terminal screw torque

Determined by installed terminal base

Dimensions (with module
installed)

94H x 94W x 69D mm

(3.7H x 3.7W x 2.7D inch)

Enclosure

None (open-style)

Wiring category

(1)

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication

1770-4.1

.

2 - on signal ports

Wire size

Determined by installed terminal base

IEC temp code

T4 (1794-OW8XT)

T5 (1794-OW8, 1794-OW8K)

North American temp code

T4 (1794-OW8XT)

T5 (1794-OW8, 1794-OW8K)

Press down to open

45282