General specifications – Rockwell Automation 1794-AENTR_AENTRXT FLEX I/O Dual Port EtherNet/IP Adapter Module Installation Instructions User Manual

Page 5

Advertising
background image

FLEX I/O

Dual Port EtherNet/IP Adapter Modules 5

Publication 1794-IN131A-EN-P - January 2012

General Specifications

Indicator

Status

Link 1 or Link 2 (individually)

Off

No link exists. Verify network cabling. Correct as necessary.

Solid green

Link exists at 100 Mbps.

Flashing green

I/O is being transmitted or received at 100 Mbps.

Flashing yellow

I/O is being transmitted or received at 10 Mbps.

Solid yellow

Link exists at 10 Mbps.

Module Status Indicator

Off

No power. Adapter does not have 24V DC power. Make sure
power is being supplied to the adapter.

Flashing green

Standby. Adapter not configured. Configure adapter.

Green

Operational. Adapter operating correctly. No action
required.

Flashing red

Minor fault. A recoverable fault has been detected. This
could be caused by an incorrect or inconsistent
configuration.

Check configuration and reconfigure as needed.

Solid red

Major fault. An unrecoverable fault has been detected.
Recycle power to the adapter. If this does not clear the
fault, replace the adapter.

Flashing red/green

Self test. Adapter performing power-up self test. Wait until
completed.

Network Status Indicator

Off

Not powered. No IP address. Adapter is not powered or
does not have an IP address.

Verify there is power and the adapter is correctly wired to
the power supply.

Make sure the adapter is configured.

Flashing green

No connection. Adapter has obtained an IP address, but has
no established connections.

Green

CIP connections. Adapter has an IP address and at least one
established connection.

Flashing red

Connection timeout. One or more of the connections in
which the adapter is the target has timed out.

Red

Duplicate IP address. Adapter has detected that its IP
address is already in use. Configure the adapter with a
unique IP address.

Flashing red/green

Self-test. Adapter performing power-up self test.

Attribute

Value

I/O capacity

8 modules

Power supply

To comply with the CE Low Voltage Directive (LVD), this
equipment must be powered from a source compliant with
the following:

Safety Extra Low Voltage (SELV) or Protected Extra Low
Voltage (PELV).

Input voltage rating,
nom

24V DC

Input voltage range

19.2…31.2V DC (includes 5% AC ripple)

Inrush current

18 A for 2 ms

Communication rate

10/100 Mbps

Indicators

Module status – red/green

Network status – red/green

Link 1 – yellow/green

Link 2 – yellow/green

FlexBus output

5.0V DC

640 mA, max

Isolation voltage

50V (continuous), Basic Insulation Type

Tested @ 1000V AC for 60 s, power to FlexBus to EtherNet

Power consumption,
max

500 mA,

400 mA @ 24V DC

Power dissipation, max 7.1 W @ 19.2V DC

Thermal dissipation

24.2 BTU/hr @ 19.2V DC

Ethernet connector

RJ45 Cat. 5

Enclosure type rating

None (open-style)

Wire size

Power conductors:

0.33…3.31 mm

2

(22…12 AWG) stranded copper wire rated

@ 75 °C (167 °F) or greater, 1.2 mm (3/64 in.) insulation
max

Wiring category

(1)

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation
Wiring and Grounding Guidelines, publication

1770-4.1

.

1 – on power ports

2 – on communication ports

North American temp
code

T5 – 1794-AENTR

T4A – 1794-AENTRXT

IEC temp code

T5 – for 1794-AENTR

T4 – for 1794-AENTRXT

Terminal screw torque 0.8 Nm (7 lb-in.)

Weight, approx.

227 g (8.01 oz)

Dimensions, HxWxD,
approx.

87.4 x 94 x 92 mm

(3.44 x 3.7 x 3.6 in.)

Advertising