Environmental Specifications

Certifications

Mounting Dimensions

The module has the following mounting dimensions.

Attribute

Value

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

0…55 °C (32…131 °F) – 1794-AENTR

-25 …70 °C (-13…158 °F) – 1794-AENTRXT

Temperature,
surrounding air, max

55 °C (131 °F) – 1794-AENTR

70 °C (158 °F) – 1794-AENTRXT

Temperature,
nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry
Heat),

IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock):

-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5 …95% non-condensing

Vibration

IEC60068-2-6 (Test Fc, Operating):

5 g @ 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

30 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

50 g

Emissions

CISPR 11:

Group 1, Class A

ESD immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz

10/m with 1 kHz sine-wave 80% AM from
2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:

±4 kV at 5 kHz on power ports

±4 kV at 5 kHz on communication ports

Surge transient
immunity

IEC 61000-4-5:

±1 kV line-line (DM) and ±2 kV line-earth(CM) on
power ports

±2 kV line-earth(CM) on communication ports

Conducted RF immunity IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from 150
kHz…80 MHz

Attribute

(when product is

marked

(1)

)

Value

c-UL-us

UL Listed Industrial Control Equipment, certified for US and

Canada. See UL File E322657.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous

Locations, certified for U.S. and Canada. See UL File E334470.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with:

EN 60079-15; Potentially Explosive Atmospheres, Protection "n"

EN 60079-0; General Requirements

EN 60079-11; Explosive Atmospheres, Protection "i"

II 3 G Ex ic nA IIC T5 Gc – for 1794-AENTR only

II 3 G Ex ic nA IIC T4 Gc – for 1794-AENTRXT only

TÜV

TÜV Certified for Functional Safety:

Capable of SIL 2

EtherNet/IP

ODVA conformance tested to EtherNet/IP specifications

KC

Korean Registration of Broadcasting and Communications

Equipment, compliant with:

Article 58-2 of Radio Waves Act, Clause 3

(1)

See the Product Certification link at

www.ab.com

for Declarations of Conformity, Certificates, and other

certification details.

WARNING

For Class I Division 2 applications, use only Class I Division 2 listed or
recognized accessories and modules approved for use within the
1794 platform.

45826

1794-AENTR
shown

Millimeters
(Inches)

80.4

(3.16)

87.4

(3.44)

94

(3.70)

1794-AENTR, 1794-AENTRXT
87.4 H x 94W x 92D

(344H x 3.7W x 3.6D)

50

(1.96)

30.4

(1.19)