Installing Block I/O

Chapter 3

3Ć5

Power Supply Requirements

An external 24V dc power supply is required to power the block. Total
current required to power the block is equal to 200mA plus an inrush of
5.5A for 10

µ

sec for each block. The supply must be able to source an

additional 100mA plus an inrush current of 400mA when a peripheral is
connected.

In addition, the external power supply should have current limiting
capabilities. The voltage range must not exceed 20.5–27.6V dc.

Wiring Requirements

Wiring cable requirements are shown in the following table.

Table 3.C

Acceptable Wiring Cables for Block I/O Connection

Use

Cable Type

With

Remote I/O Link or DIO Link

Belden 9463

PLC-2, PLC-3, PLC-5 family programmable

controllers and SLC controllers

DH-485 Data Link

Belden 9842

SLC controllers only

Input and Output wiring

Up to 14AWG

Stranded with 3/64

inch insulation

All

Figure 3.5

Remote I/O Link Wiring

Tighten screw to clamp wire.

Blue

Clear

Shield

Connection 1 2 SHD
Clear wire X

Blue wire X

Shield wire X

10832-I