Troubleshooting

Chapter 6

6Ć2

Table 6.A

Troubleshooting Chart

Indication

Probable Cause

Corrective Action

Green COMM LED on

Red POWER LED on

I/O status LED on/off

Normal indication

None required

Red POWER LED flashing

Block failed self-test, or a major fault is detected.

Cycle power to the block. If problem persists,

replace the block.

Red POWER LED off

No 24V dc power connected, or hardware fault.

Check 24V dc power to block

Green COMM LED off

No communication with processor, scanner etc.

Check that power LED is on. Make sure that

proper number of blocks are configured.

Green COMM LED flashing

Reset command (or output disable bit for SLC) has

been issued by processor or scanner.

Check program. Correct as necessary.

SLC or programmable controller not in run mode.

Place in run mode.

In this chapter you learned about the LED indicators and how to use them
to troubleshoot the block I/O module.