Install the module – Rockwell Automation 1734-IK/C POINT I/O 5V and 24V Encoder/Counter Module Installation Instructions User Manual
Page 8
 
8 POINT I/O™ 5V and 24V Encoder/Counter Modules
Publication 1734-IN005G-EN-E - September 2012
Install the Module
The module can be installed before or after base installation. Make sure that the mounting 
base is correctly keyed before installing the module into the mounting base. In addition, 
make sure the mounting base locking screw is positioned horizontal referenced to the base.
1. Using a bladed screwdriver, rotate the keyswitch on the mounting base clockwise
until the number required for the type of module being installed aligns with the 
notch in the base.
2. Make certain the DIN rail locking screw is in the horizontal position. You cannot
insert the module if the locking mechanism is unlocked.
3. Insert the module straight down into the mounting base and press to secure. The
module locks into place.
WARNING: When you insert or remove the module while backplane power is 
on, an electrical arc can occur. This could cause an explosion in hazardous 
location installations.
Be sure that power is removed or the area is nonhazardous before proceeding. 
Repeated electrical arcing causes excessive wear to contacts on both the 
module and its mating connector. Worn contacts may create electrical 
resistance that can affect module operation.