SLC™ 500 4-Channel Thermocouple/mV Input Module 11

Publication 1746-IN010D-EN-P - June 2004

Terminal Wiring

The thermocouple module contains a green, 18-position, removable terminal block.
The terminal pin-out is shown below.

Terminal screws accept a maximum of two #14 AWG (2 mm

2

) wires. Tighten

terminal screws only tight enough to immobilize wires. Maximum torque on
terminal screws is 0.7 to 0.9 Nm (6 to 8 in-lbs).

ATTENTION

Disconnect power to the SLC before attempting to install,
remove, or wire the removable terminal wiring block.

(Terminal Block Spare Part Catalog Number 1746-RT32)

CJC A+

CJC A-

CJC Assembly

Shield

Shield

Shield

Shield

Shield

CJC B+

CJC B-

CJC Assembly

Release Screw Max. Torque =
0.7 to 0.9 Nm (6 to 8 in-lb)

Release Screw Max. Torque =
0.7 to 0.9 Nm (6 to 8 in-lb)

Channel 0+

Channel 0-

Channel 1+

Channel 1-

Channel 2+

Channel 2-

Channel 3+

Channel 3-

Analog Common

[see

(1)

below]

(1)

Replacing a Series A thermocouple module with a Series B module requires that the bottom right terminal (which was
SHIELD on Series A modules) no longer be connected to CHASSIS GROUND if it was previously. Use one of the other
SHIELD terminals.