Rockwell Automation 1746-NT4 SLC 500 Thermocouple/mV Input Module Installation Instructions User Manual
Page 22

22 SLC™ 500 4-Channel Thermocouple/mV Input Module
Publication 1746-IN010D-EN-P - June 2004
Thermocouple/mV Input Module Accuracy
Filter Frequency and Step Response Time
Channel Sampling Time for Each Filter Frequency
Input Type
With Autocalibration
(1)
(1)
Assumes the module terminal block temperature is stable.
Without Autocalibration
Maximum Error at
+25°C
Maximum Error at
+77°F
Temperature Drift
(0°C to +60°C)
J
±1.06°C
±1.91°F
±0.0193°C/°C, °F/°F
K
±1.72°C
±3.10°F
±0.0328°C/°C, °F/°F
T
±1.43°C
±2.57°F
±0.0202°C/°C, °F/°F
E
±0.72°C
±1.3°F
±0.0190°C/°C, °F/°F
S
±3.61°C
±6.5°F
±0.0530°C/°C, °F/°F
R
±3.59°C
±6.46°F
±0.0530°C/°C, °F/°F
B
±3.12°C
±5.62°F
±0.0457°C/°C, °F/°F
N
±1.39°C
±2.5°F
±0.0260°C/°C, °F/°F
±50 mV
±50 µV
±50 µV
±1.0 µV/°C, ±1.8 µV/°F
±100 mV
±50 µV
±50 µV
±1.5 µV/°C, ±2.7 µV/°F
Filter Frequency
50 Hz NMR
(1)
(1)
Normal Mode Rejection
60 Hz NMR
1
Cut-Off
Frequency
Step Response
10 Hz
100 dB
100 dB
2.62 Hz
300 msec
50 Hz
100 dB
-
13.1 Hz
60 msec
60 Hz
-
100 dB
15.72 Hz
50 msec
250 Hz
-
-
65.5 Hz
12 msec
CJC Update Time
Channel Sampling Time
(1)
(1)
all values ±1 msec
250 Hz Filter
60 Hz Filter
50 Hz Filter
10 Hz Filter
14 msec
12 msec
50 msec
60 msec
300 msec