Physical specifications, Environmental specifications – Rockwell Automation 1746-NT8 SLC 500 Thermocouple/mV Analog Input Module User Manual User Manual
Page 82

Publication 1746-UM022B-EN-P - January 2005
A-2 Module Specifications
Physical Specifications
Environmental
Specifications
LED Indicators
9 green status indicators, one for each of 8 channels and
one for module status
Module ID Code
3533
Recommended Cable:
for thermocouple inputs…
for mV inputs…
Appropriate shielded twisted pair thermocouple
extension wire
(1)
Belden™ 8761 or equivalent
(1) Refer to the thermocouple manufacturer for the correct extension wire.
Maximum Wire Size
One 14 AWG wire or two 22 AWG wires per terminal
Operating Temperature
0°C to +60°C (+32°F to +140°F)
Storage Temperature
-40°C to +85°C (-40°F to +185°F)
Relative Humidity
5% to 95% (without condensation)
Certification
UL and CUL approved
Hazardous Environment Classification
Class I Division 2 Hazardous Environment
Groups A, B, C, D
EMC
CE compliant for all applicable directives
C-Tick compliant for all applicable acts