Thermocouple – Rockwell Automation 1746-NT8 SLC 500 Thermocouple/mV Analog Input Module User Manual User Manual

Page 86

Advertising
background image

Publication 1746-UM022B-EN-P - January 2005

A-6 Module Specifications

uV Err, ±100mV Span, Prop Cts, 60 Hz, 60°C

Thermocouple

The following table provides the total error expected of the
thermocouple based on the thermocouple type, and the given
reference point, at 25°C. The calculations assumed typical
hardware/software error and typical CJC accuracy at 25°C.

The following table provides the total error expected over the
temperature range of the module (0 to 60°C) for each thermocouple
based upon the type, and the given reference point, at the extremes of
the temperature range (0 or 60°C). The calculations are based on
maximum hardware/software error and maximum CJC inaccuracy
over temperature.

0.00

10.00

20.00

30.00

40.00

50.00

60.00

70.00

80.00

90.00

-100

-99.92-99.84-99.76-99.68 -99.6-99.52-50.16-50.08 -50 -49.92-49.84 -0.18

-0.1 -0.02 0.06 0.14 49.8 49.8849.96 50.04 50.12 50.2 99.5699.64 99.72 99.8 99.88 99.96

uV Error

mV Input

uV D

e

viatio

n

Thermocouple Type

Thermocouple Reference Point Error

J

+275°C (+527°F)

±1.4°C (±2.52°F)

K

+550°C (+1022°F)

±1.5°C (±2.7°F)

T

+65°C (+149°F)

±1.3°C (±2.34°F)

E

+365°C (+689°F)

±1.3°C (±2.34°F)

R

+885°C (+1625°F)

±3.6°C (±6.48°F)

S

+885°C (+1625°F)

±3.4°C (±6.12°F)

B

+1060°C (+1940°F)

±2.7°C (±4.86°F)

N

+500°C (+932°F)

±1.3°C (±2.34°F)

Advertising