Rockwell Automation Publication 1738-UM005A-EN-P - July 2013

67

Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Chapter 5

5. Select the Connection tab to set the RPI value.

RPI is selectable since it is a direct connection.

Note that RPI is selectable on the screen because you are adding an analog
module and an RPI value must be assigned for the module.

6. Enter 50.0 for the RPI and click OK to save the configuration.

The analog current input module appears in the I/O Configuration
indented under the 1738-AENT/B adapter.

Add the Analog Current Output Module

1. Highlight the 1738-AENT/B adapter under the I/O Configuration

folder, right-click and select New Module.

IMPORTANT

To avoid overloading the 1738-AENT/B adapter, it is recommended
that the RPI be no less than 50.0 ms.