Compact 1769-OF4CI Isolated Analog Output Module 21
Rockwell Automation Publication 1769-IN075B-EN-P - August 2010
Define
Indicate this
These bit settings
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
Program
(Idle) to Fault
Enable
Program (Idle)
Mode Data
Applied
(1)
0
Fault Mode Data
Applied
(1)
1
Hold for
Initialization
Disabled
0
Enabled
1
Program
(Idle) Mode
Hold Last State
(1)
0
User-Defined
Value
(1)
1
Fault Mode
Hold Last State
(1)
0
User-Defined
Fault Value
(1)
1
Enable
Ramping
Disabled
0
Enabled
1
System
Interrupt
High Clamp
Disabled
0
Enabled
(1)
1
System
Interrupt Low
Clamp
Disabled
0
Enabled
(1)
1
Enable
Channel
Disabled
0
Enabled
1
(1)
These functions are not supported by all controllers (for example, MicroLogix 1500) using any
configuration method. Refer to your controller manual for details.
Define
Indicate this
These bit settings
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
Output
Range
Select
0…20 mA DC
0
0
0
4…20 mA DC
0
0
1
Output
Data
Select
Raw/Proportional
Counts
0
0
0
Engineering Units
0
0
1
Scaled for PID
0
1
0
Percent Range
0
1
1