Compact 1769-OF4CI Isolated Analog Output Module 23

Rockwell Automation Publication 1769-IN075B-EN-P - August 2010

Specification

1769-OF4CI

Analog Normal Operating Ranges

(1)

0 to 20 mA, 4 to 20 mA

Full Scale Analog Ranges

(1)

0 to 21 mA, 3.2 to 21 mA

Number of Outputs

4 isolated differential

Bus Current Draw (max.)

5V, 165mA
24V, 110mA

Heat Dissipation

2.68 Total Watts (All points - 21 mA into
250

Ω - worst case calculated.)

Digital Resolution Across Full Range

16 bits (unipolar)
+4 to +20 mA: 15.59 bits, 0.323 µA/bit
0 to +20 mA: 15.91 bits, 0.323 µA/bit

Conversion Rate (all channels) max.

110 ms

Step Response to 63%

(2)

<2.9 ms

Resistive Load on Current Output

0 to 500

Ω (includes wire resistance)

Max. Inductive Load

0.1 mH

Field Calibration

None required

Overall Accuracy

(3)

±0.35% full scale at 25°C

(1)

The over- or under-range flag will come on when the normal operating range (over/under) is exceeded.
The module will continue to convert the analog output up to the maximum full scale range. The flag
automatically resets when within the normal operating range unless configured to latch.

(2)

Step response is the period of time between when the D/A converter was instructed to go from
minimum to full range until the device is at 63% of full range.

(3)

Includes offset, gain, drift, non-linearity and repeatability error terms.